Schneider Electric 989-1020 TR3624-120-60, 3600W, 24V, 120VAC inverter
Product Description
| Product
data sheet |
989-1020 |
| Characteristics |
Xantrex TR - Trace Series
inverter / charger |
| |
TR3624-120-60 - 3600VA 30A
60Hz |
| Main |
|
| Range of product |
Xantrex TR |
| Device short name |
TR3624-120-60 |
| Product or component |
Trace
Series inverter / charger |
| Type of signal |
Modified
sine wave - invert mode |
| Continuous power |
3600
VA (output) - invert mode |
| |
7200 VA overload 10 s |
| Complementary |
|
| Output voltage |
120 V rms AC - invert mode |
| Output current |
30
A |
| Peak output current |
120
A +/- 10 % - short circuit 10 s |
| Network frequency |
60
Hz |
| Power range |
5...240
W - invert mode |
| Cos phi |
0.8...1
leading or lagging - invert mode |
| |
0.93 (input) -
bypass/charge mode |
| Input voltage limits |
65...140
V AC wide-charge - bypass/charge mode |
|
95...140 V AC narrow-charge
- bypass/charge mode |
| |
22...30 V DC - invert mode |
| Input current |
0.2
A DC no load - search mode - invert mode |
|
186 A DC rated current -
invert mode |
| |
19.5 A AC maximum charge
rate - bypass/charge mode |
| Input frequency |
55...64
Hz AC narrow-charge & pass-through - bypass/charge mode |
|
55...68 Hz AC wide-charge -
bypass/charge mode |
| |
41...68 Hz AC wide
pass-through - bypass/charge mode |
| Charging current |
10...70
A DC adjustable - bypass/charge mode |
| Efficiency |
>
94 % peak - invert mode |
| Relay type |
Automatic
transfert relay 30 A |
| Transfer time |
<
40 ms wide-charge |
| |
< 20 ms narrow-charge |
| Device mounting |
Wall
mounted |
| Provided equipment |
Battery
temperature sensor included for temperature compensation |
| Height |
184
mm |
| Width |
216
mm |
| Length |
546
mm |
| Product weight |
20
kg |
| Environment |
|
| Ambient air temperature for operation |
0...50 °C |
| Standards |
CSA
107.1 |
| |
UL 1741 |
| Product certifications |
CSA |
|
FCC Class B |
| |
Industry Canada |
| Marking |
CE |
|
|